{"id":1967,"date":"2019-10-14T23:00:25","date_gmt":"2019-10-14T23:00:25","guid":{"rendered":"http:\/\/bryceautomation.com\/?p=1967"},"modified":"2020-11-30T20:11:30","modified_gmt":"2020-11-30T20:11:30","slug":"slc-500-remote-i-o","status":"publish","type":"post","link":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/","title":{"rendered":"SLC-500 Remote I\/O (1747-SN)"},"content":{"rendered":"\n<h3 class=\"wp-block-heading\">Introduction to SLC-500 Remote I\/O (1747-SN)<\/h3>\n\n\n\n<p>There are many reasons to use SLC-500 Remote I\/O (1747-SN).  Imagine a conveyor system.  Ten thousand feet from the local processor chassis, you have 256 points of I\/O.  With Remote I\/O, you could mount a chassis up to 10,000 feet from the local processor with a Remote I\/O adapter, and the processor could control the I\/O directly.  This would eliminate the need to run 256 cables from the remote location all the way back to the processor.   <\/p><div id=\"bryce-3403960618\" class=\"bryce-afterfirst bryce-entity-placement\"><script async src=\"\/\/pagead2.googlesyndication.com\/pagead\/js\/adsbygoogle.js?client=ca-pub-8316758073402323\" crossorigin=\"anonymous\"><\/script><ins class=\"adsbygoogle\" style=\"display:block;\" data-ad-client=\"ca-pub-8316758073402323\" \ndata-ad-slot=\"7728240895\" \ndata-ad-format=\"auto\"><\/ins>\n<script> \n(adsbygoogle = window.adsbygoogle || []).push({}); \n<\/script>\n<\/div>\n\n\n\n<p>We also use Remote I\/O to increase the number of I\/O points the processor controls.  Sometimes the amount of I\/O we need wouldn&#8217;t normally fit in a standard SLC chassis, or even extended local I\/O on the SLC.<\/p>\n\n\n\n<p>A key concept to understand is that the 1747-SN (Scanner  Module) converts PLC-5 typed addressing into SLC addressing.  (Racks and Groups into Slots and Words)<\/p>\n\n\n\n<p>Consider the Following Image:<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"422\" height=\"359\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image.png\" alt=\"\" class=\"wp-image-1968 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image.png 422w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-300x255.png 300w\" data-sizes=\"(max-width: 422px) 100vw, 422px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 422px; --smush-placeholder-aspect-ratio: 422\/359;\" \/><\/figure>\n\n\n\n<h3 class=\"wp-block-heading\">SLC-500 Remote I\/O (1747-SN) Terms<\/h3>\n\n\n\n<h4 class=\"wp-block-heading\">Memory<\/h4>\n\n\n\n<h5 class=\"wp-block-heading\"><strong>Bit <\/strong>\n<\/h5>\n\n\n\n<p>This is the\nsmallest unit of information the processor can handle.  A bit can\nonly have 2 states:  <strong>On or Off<\/strong>, True or False, 1 or 0, Yes or\nNo (however you wish to express it)<\/p>\n\n\n\n<h5 class=\"wp-block-heading\"><strong>Word<\/strong><\/h5>\n\n\n\n<p>In the PLC-5 and\nSLC, a word is a memory location consisting of <strong>16 bits<\/strong> by\ndefinition.  The entire input and output data tables are made up of\n16 bit words.  You can see this clearly when the RADIX is switched to\nBINARY.<\/p>\n\n\n\n<h5 class=\"wp-block-heading\"><strong>Group<\/strong><\/h5>\n\n\n\n<p>The Group is a\nPLC-5 Term.  A Group is a memory location consisting of one word of\ninput, and one word of output.  (<strong>An input\/output pair<\/strong>). \n<\/p>\n\n\n\n<h5 class=\"wp-block-heading\"><strong>Rack<\/strong><\/h5>\n\n\n\n<p>The rack is another PLC-5 term.  A Rack is a memory location consisting of 8 Groups.  Important:  <strong>A RACK ALWAYS consists of 8 Groups<\/strong>.  The Rack is not the same as a chassis on Remote I\/O.  A chassis can be small enough that it does not take up an entire rack of memory, or may be large enough that it consumes more than one rack of memory.  Please do not get the terms Rack and Chassis confused.<\/p>\n\n\n\n<h4 class=\"wp-block-heading\">Other Terms<\/h4>\n\n\n\n<h5 class=\"wp-block-heading\"><strong>Addressing Mode<\/strong><\/h5>\n\n\n\n<p>Switches located\non bank #3 on the SLC adapter, or the backplane of a PLC-5 chassis\ndetermine the addressing mode.  In 1-slot addressing, an entire group\nis dedicated to each slot.  In 2-slot addressing, a group is\ndedicated to every 2 slots.  In \u00bd-slot addressing (less common), a\ngroup is dedicated to every \u00bd slot (This means you get 2 groups for\neach slot).<\/p>\n\n\n\n<h5 class=\"wp-block-heading\"><strong>Baud Rate<\/strong><\/h5>\n\n\n\n<p>The baud rate is\nthe speed at which communication takes place on the network.  All\ndevices on the same network <strong>MUST<\/strong> run at the same baud rate. \nWith a baud rate set set 57.6K, communication is possible for network\ndistances up to 10,000 feet.  As the baud rate increases, the allowed\nnetwork distance shortens.  For a baud rate of 115.2K, your network\nis limited to 5000 feet, and for a baud rate setting of 230.4K, the\nmaximum network distance allowed is 2500 feet.<\/p>\n\n\n\n<h5 class=\"wp-block-heading\"><strong>Terminators<\/strong><\/h5>\n\n\n\n<p>BOTH ENDS of the\nnetwork must be terminated to hold the network impedance at the\nproper value.  The value of the resistor depends on the baud rate. \nFor baud rates of  57.6K and 115.2K, you will terminate both ends\nwith a 150 Ohm resistor.  For 230.4K, use an 82 Ohm resistor.  The\nresistor should be  \u00bd Watt (non-inductive) with a 1% tolerance.<\/p>\n\n\n\n<p><em>(Note:  For extended node capability (Not as common), you will always use an 82 Ohm resistor) <\/em> <\/p>\n\n\n\n<h3 class=\"wp-block-heading\">SLC-500 Remote I\/O (1747-SN) <strong>Physical Topology<\/strong><\/h3>\n\n\n\n<p>\nThere are no restrictions on the space between devices on the network\nas long as the total network length does not exceed the specification\nfor the chart below <em>(with no extended node capability)<\/em><\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>\n\t\t\t\tBaud Rate\n\t\t\t<\/th><th>\n\t\t\t\tMaximum Network Distance\n\t\t\t<\/th><th>\n\t\t\t\tValue of Terminating Resistor\n\t\t\t<\/th><\/tr><\/thead><tbody><tr><td>\n\t\t\t\t57.6 Kbps\n\t\t\t<\/td><td>\n\t\t\t\t10,000 &#8216;\n\t\t\t<\/td><td>\n\t\t\t\t150 Ohm\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t115.2 Kbps\n\t\t\t<\/td><td>\n\t\t\t\t5,000 &#8216;\n\t\t\t<\/td><td>\n\t\t\t\t150 Ohm\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t230.4 Kbps\n\t\t\t<\/td><td>\n\t\t\t\t2,500 &#8216;\n\t\t\t<\/td><td>\n\t\t\t\t82 Ohm\n\t\t\t<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p><strong>Here is a typical network. <\/strong> <\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"665\" height=\"168\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-1.png\" alt=\"\" class=\"wp-image-1969 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-1.png 665w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-1-300x76.png 300w\" data-sizes=\"(max-width: 665px) 100vw, 665px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 665px; --smush-placeholder-aspect-ratio: 665\/168;\" \/><\/figure>\n\n\n\n<p> Note:  When wiring the Phoenix connectors on the scanner and adapters, you should never have more than 2 wires under any 1 screw terminal.  Your devices are daisy-chained together or connected in a trunkline\/dropline configuration with a special connector box.  Star topologies are NOT supported.<\/p>\n\n\n\n<p> Ensure the shield is only grounded at one end.  Shielding the ground a both ends could cause a ground loop.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\"><strong>Gathering\nInformation:<\/strong><\/h3>\n\n\n\n<p>The are 4 things you must know about\nany device that runs on Remote I\/O.  \n<\/p>\n\n\n\n<ul class=\"wp-block-list\"><li>\nRack\n\t<\/li><li>\nStarting Group\n\t<\/li><li>\nBaud Rate\n\t<\/li><li>\nSize (In Racks) \n\t\n<\/li><\/ul>\n\n\n\n<p>If we had a chassis running on remote\nI\/O, and our system was down, we could remove the adapter from the\nchassis to gather all the information we need.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Rack Number (for ASB) when used with SLC-500 Remote I\/O (1747-SN)<\/h3>\n\n\n\n<p>Below is a SLC adapter module, A PLC-5 Adapter module, and the PLC-5 backplane.   Let&#8217;s explain how to find or set the <strong>Rack Number<\/strong> for each type of adapter:<\/p>\n\n\n\n<p>The SLC adapter (top)  PLC-5 Adapter (bottom):   Switches  Switches 1 to 6 on Switch Bank 1:<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"208\" height=\"124\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-2.png\" alt=\"\" class=\"wp-image-1970 lazyload\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 208px; --smush-placeholder-aspect-ratio: 208\/124;\" \/><figcaption><br><\/figcaption><\/figure>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"283\" height=\"80\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-3.png\" alt=\"\" class=\"wp-image-1971 lazyload\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 283px; --smush-placeholder-aspect-ratio: 283\/80;\" \/><\/figure>\n\n\n\n<p>Here are a few settings for the\nswitches<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>\n\t\t\t\tRack #\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 1\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 2\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 3\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 4\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 5\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 6\n\t\t\t<\/th><\/tr><\/thead><tbody><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t4\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t5\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t6\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t7\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h3 class=\"wp-block-heading\"><strong>Starting\nModule Group (SMG)  <\/strong>\n<\/h3>\n\n\n\n<p>The Starting Module Group (SMG) can be found by looking at switches 7 and 8 on Switch Bank 1 on either the SLC Adapter (top) or the PLC-5 Adapter (bottom)<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"206\" height=\"135\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-4.png\" alt=\"\" class=\"wp-image-1973 lazyload\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 206px; --smush-placeholder-aspect-ratio: 206\/135;\" \/><\/figure>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"365\" height=\"66\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-5.png\" alt=\"\" class=\"wp-image-1974 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-5.png 365w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-5-300x54.png 300w\" data-sizes=\"(max-width: 365px) 100vw, 365px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 365px; --smush-placeholder-aspect-ratio: 365\/66;\" \/><\/figure>\n\n\n\n<p>Use the following table to determine\nthe Starting Module Group:<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>\n\t\t\t\tStarting Module Group\n\t\t\t<\/th><th>\n\t\t\t\tSwitch #7\n\t\t\t<\/th><th>\n\t\t\t\tSwitch #8\n\t\t\t<\/th><\/tr><\/thead><tbody><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t4\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t6\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p>Why have a Starting Module Group?  Remember the difference between a Rack and a Chassis.  A Rack is a memory location, and a chassis is the physical device that modules are placed in.  A Chassis could be so small that it only consumes half a rack of memory (Groups 0 to 3), so then we could put another chassis in the same rack starting at module group 4, then it would consume groups 4-7.  Below is an example of this.  All 8 groups of Rack 1 are consumed by 2 chassis.   <\/p>\n\n\n\n<h3 class=\"wp-block-heading\"><strong>Baud\nRate:<\/strong><\/h3>\n\n\n\n<p>The baud rate is the speed at which\ncommunication takes place on the network.  All devices on the same\nremote I\/O network must run the same baud rate.  \n<\/p>\n\n\n\n<p>The baud rate switches for the PLC-5\nand the SLC are in the same location on switch bank 2, but the charts\nare separate for determining the baud rate.  \n<\/p>\n\n\n\n<p><em><strong>SLC Adapter  (Switch Bank 2 \u2013\nSwitches 1 and 2):<\/strong><\/em><\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>\n\t\t\t\tBaud Rate\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 1\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 2\n\t\t\t<\/th><\/tr><\/thead><tbody><tr><td>\n\t\t\t\t57.6 K\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t115.2K\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t230.4K\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p><em><strong>PLC Adapter (Switch Bank 2 \u2013\nSwitches 1 and 2)<\/strong><\/em><\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>\n\t\t\t\tBaud Rate\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 1\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 2\n\t\t\t<\/th><\/tr><\/thead><tbody><tr><td>\n\t\t\t\t57.6K\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t115.2K\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t230.4K\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h3 class=\"wp-block-heading\"><strong>Image\nSize:<\/strong><\/h3>\n\n\n\n<p>The next piece of\ninformation we need to gather is the image size.  This can be done by\nlooking at the backplane switch on the PLC-5 Adapter&#8217;s chassis, or\nSwitch #3 on the SLC Adapter.  <em>(Note:  Since there are no\nbackplane switches on the SLC, switch bank 3 was necessary on the SLC\nadapter to handle the functions of the backplane switch on the PLC-5\nchassis)<\/em><\/p>\n\n\n\n<p>\nOnce we determine the addressing mode, we can figure out what size\nthe chassis is.  Let&#8217;s find what addressing mode your chassis is\nconfigured for, then we&#8217;ll figure out the size.<\/p>\n\n\n\n<p>\nLook at Switch Bank 3 on the SLC Adapter, or the Backplane switches\non the PLC-5.  (Switches 5 and 6)<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>\n\t\t\t\tAddressing Mode\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 5\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 6\n\t\t\t<\/th><\/tr><\/thead><tbody><tr><td>\n\t\t\t\t2- Slot\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1-Slot\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t\u00bd Slot\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h3 class=\"wp-block-heading\">\n<strong>Deriving the Size:<\/strong><\/h3>\n\n\n\n<p>\nRemember the definition of Addressing Mode:<\/p>\n\n\n\n<p>\nSwitches located on bank #3 on the SLC adapter, or the backplane of a\nPLC-5 chassis determine the addressing mode.  In 1-slot addressing,\nan entire group is dedicated to each slot.  In 2-slot addressing, a\ngroup is dedicated to every 2 slots.  In \u00bd-slot addressing (less\ncommon), a group is dedicated to every \u00bd slot (This means you get 2\ngroups for each slot).<\/p>\n\n\n\n<p>\nLet&#8217;s look at some examples \u2013 You will notice the adapter is not\ncounted as an I\/O group:<\/p>\n\n\n\n<p>\n<strong>1- Slot Addressing<\/strong> \u2013 Each group is dedicated to a slot \n(each chassis below consumes \u00bd Rack)<\/p>\n\n\n\n<p>\n<strong>2-Slot Addressing<\/strong> \u2013 Each group is dedicated to every 2 slots\n (each chassis below consumes \u00bc Rack)<\/p>\n\n\n\n<p> <strong>\u00bd- Slot Addressing<\/strong> \u2013 Each group is dedicated to every \u00bd slot.  (2 groups per slot)  Each chassis below consumes an entire rack of memory.  This mode is generally used with 32 point modules.<\/p>\n\n\n\n<h4 class=\"wp-block-heading\">Sizing Chart<\/h4>\n\n\n\n<p> You can use the chart below as a cross reference to derive the size if you know how many slots are in the chassis, and the addressing mode.   <\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>\n\t\t\t\tPLC-5 Chassis Size\n\t\t\t<\/th><th>\n\t\t\t\t2-Slot Addressing\n\t\t\t<\/th><th>\n\t\t\t\t1-Slot Addressing\n\t\t\t<\/th><th>\n\t\t\t\t\u00bd Slot Addressing\n\t\t\t<\/th><\/tr><\/thead><tbody><tr><td>\n\t\t\t\t4-Slots\n\t\t\t<\/td><td>\n\t\t\t\t\u00bc Rack\n\t\t\t<\/td><td>\n\t\t\t\t\u00bd Rack\n\t\t\t<\/td><td>\n\t\t\t\tFULL (1 Rack)\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t8-Slots\n\t\t\t<\/td><td>\n\t\t\t\t\u00bd Rack\n\t\t\t<\/td><td>\n\t\t\t\tFULL (1 Rack)\n\t\t\t<\/td><td>\n\t\t\t\t2 Racks\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t12-Slots\n\t\t\t<\/td><td>\n\t\t\t\t\u00be Rack\n\t\t\t<\/td><td>\n\t\t\t\t1 \u00bd Racks\n\t\t\t<\/td><td>\n\t\t\t\t3 Racks\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t16 Slots\n\t\t\t<\/td><td>\n\t\t\t\tFULL (1 Rack)\n\t\t\t<\/td><td>\n\t\t\t\t2 Racks\n\t\t\t<\/td><td>\n\t\t\t\t4 Racks\n\t\t\t<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p>\nThe SLC chassis do not generally come out to even numbers, but are\ngenerally set according to the guidelines.  For example:  If you have\nan SLC chassis in 1 slot addressing, the adapter would go in the\nfirst slot of the chassis.  If there were six other slots left in the\nchassis, we would say the chassis consumes \u00be or a rack.  Because the\nSLC chassis do not always come out even, an additional switches are\nused on the SLC chassis to manually assign the size.  This size\nsetting is located on Switch Bank 2, switches 5-8. <\/p>\n\n\n\n<h3 class=\"wp-block-heading\"> <strong>SLC Size Settings for the 1747-ASB  (SLC only)<\/strong><\/h3>\n\n\n\n<p>The next page will explain each setting configuration.  This step is NOT required for a PLC-5 chassis.  The adapter automatically recognizes the size in the PLC-5.<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>\n\t\t\t\tImage Size \n\t\t\t\t\n\t\t\t\t(In Groups)\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 5\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 6\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 7\n\t\t\t<\/th><th>\n\t\t\t\tSwitch 8\n\t\t\t<\/th><\/tr><\/thead><tbody><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t4\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t6\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t8\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t10\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t12\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t14\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t16\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t18\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t20\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t22\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t24\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t26\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t28\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t30\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tON\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t32\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><td>\n\t\t\t\tOFF\n\t\t\t<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h3 class=\"wp-block-heading\"> <strong>Making it<\/strong> work<strong>!<\/strong><\/h3>\n\n\n\n<p>\nYour lawnmower will generally run if you have 2 things:  Gas and\nSpark.<\/p>\n\n\n\n<p>\nThe SLC adapter will generally run if you do 2 things:  Check or Set\nthe Adapter Parameters, and Tell the scanner to scan the adapter. \n(Your cabling system must also be in tact)<\/p>\n\n\n\n<p>\nFor our classroom system, write down the parameters you found on the\nadapter you will be scanning:<\/p>\n\n\n\n<p>\nRack ___________<\/p>\n\n\n\n<p>\nSMG ___________<\/p>\n\n\n\n<p>\nBaud Rate _______<\/p>\n\n\n\n<p> Size ____________<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Set up the Project for SLC-500 Remote I\/O (1747-SN)<\/h3>\n\n\n\n<p> Now we need to tell the scanner to scan the adapter. We&#8217;ll do that in the I\/O Configuration in RSLogix 500.   Be sure the 1747-SN module is in the I\/O Configuration.  If not,  Just drag the scanner module from the list of Available modules, and drop it into the appropriate slot.   <\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"629\" height=\"227\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-6.png\" alt=\"\" class=\"wp-image-1975 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-6.png 629w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-6-300x108.png 300w\" data-sizes=\"(max-width: 629px) 100vw, 629px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 629px; --smush-placeholder-aspect-ratio: 629\/227;\" \/><\/figure>\n\n\n\n<p> The series of the scanner is printed on the side of the module, so be sure to select the appropriate series.<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"247\" height=\"121\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-7.png\" alt=\"\" class=\"wp-image-1976 lazyload\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 247px; --smush-placeholder-aspect-ratio: 247\/121;\" \/><\/figure>\n\n\n\n<p>\nDouble click the scanner module in the I\/O Configuration, or\nhighlight the scanner, and click \u201cAdvanced Configuration\u201d. \n<\/p>\n\n\n\n<p> Choose \u201cEdit &#8216;G&#8217; Data\u201d  This is the scanner confiGuration data.<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"401\" height=\"156\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-8.png\" alt=\"\" class=\"wp-image-1977 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-8.png 401w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-8-300x117.png 300w\" data-sizes=\"(max-width: 401px) 100vw, 401px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 401px; --smush-placeholder-aspect-ratio: 401\/156;\" \/><\/figure>\n\n\n\n<p> Next, set up the scanner to scan your adapter(s).  In this example, I&#8217;m going to scan Rack 3, SMG 0, \u00bc Rack.  Be aware that the DIP switches on the Scanner module itself must be set up for the same Baud Rate as the adapter, or vice-versa.<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"450\" height=\"418\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9.png\" alt=\"\" class=\"wp-image-1978 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9.png 450w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9-300x279.png 300w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9-270x250.png 270w\" data-sizes=\"(max-width: 450px) 100vw, 450px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 450px; --smush-placeholder-aspect-ratio: 450\/418;\" \/><\/figure>\n\n\n\n<p> You are ready to download and test your work.  Make sure the Comms light is solid green on the scanner, and that the adapter is active.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\"> <strong>Interpreting the Data<\/strong> for SLC-500 Remote I\/O (1747-SN)<\/h3>\n\n\n\n<p>\nWe stated earlier that the SLC does not understand the racks and\ngroups that all remote I\/O addressing uses.  These Racks and Groups\nmust be \u201ctranslated\u201d to slots and words.<\/p>\n\n\n\n<p>\nIn this example, we only have one slot to work with for all Remote\nI\/O.  That is slot 1.  Any device that is wired to the scanner will\nshow up on a word in slot 1.  \n<\/p>\n\n\n\n<p> Let&#8217;s look at the input data table.  (Note:  The output table will be very similar for slot 1).<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"571\" height=\"201\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-10.png\" alt=\"\" class=\"wp-image-1979 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-10.png 571w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-10-300x106.png 300w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-10-570x201.png 570w\" data-sizes=\"(max-width: 571px) 100vw, 571px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 571px; --smush-placeholder-aspect-ratio: 571\/201;\" \/><\/figure>\n\n\n\n<p>\nYou will notice that by scrolling down, there are 32 words total for\nslot 1 (0 to 31).  The output table is the same.  \n<\/p>\n\n\n\n<h3 class=\"wp-block-heading\"><strong>Lets do the\nmath:<\/strong><\/h3>\n\n\n\n<ul class=\"wp-block-list\"><li>\n\n\tRemember that a Group is 1 word of input AND on word of output (an\n\tinput \/ output pair).\n\t\n\t\n<\/li><li>\n\n\tIn slot 1, we have 32 words of input AND 32 words of output.\n\t\n\t\n<\/li><\/ul>\n\n\n\n<ul class=\"wp-block-list\"><li>\n\n\tTherefore, we have 32 Groups in slot 1\n\t\n\t\n\t<\/li><li>\n\n\tWe know there are 8 groups in a Rack\n<\/li><\/ul>\n\n\n\n<ul class=\"wp-block-list\"><li>\n\n\tTherefore we have 4 Racks available in slot 1  (32\/8)\n<\/li><\/ul>\n\n\n\n<p> These 4 racks are going to be numbered 0 to 3 \u2013 Let&#8217;s visually look and see how these 32 words are broken down into racks.<\/p>\n\n\n\n<h4 class=\"wp-block-heading\">Addressing Chart<\/h4>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>\n\t\t\t\tRack #\n\t\t\t<\/th><th>\n\t\t\t\tGroup #\n\t\t\t<\/th><th>\n\t\t\t\tSLC Address (E = Slot #\n\t\t\t\tof Scanner T = type (I or O))\n\t\t\t<\/th><\/tr><\/thead><tbody><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t0\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t1\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t2\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t3\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\t4\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t4\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\t5\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t5\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\t6\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t6\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\t7\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t7\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t8\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t9\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t10\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t11\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\t4\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t12\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\t5\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t13\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\t6\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t14\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\t7\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t15\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t16\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t17\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t18\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t19\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\t4\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t20\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\t5\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t21\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\t6\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t22\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\t7\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t23\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\t0\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t24\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\t1\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t25\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\t2\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t26\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t27\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\t4\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t28\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\t5\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t29\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\t6\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t30\n\t\t\t<\/td><\/tr><tr><td>\n\t\t\t\t3\n\t\t\t<\/td><td>\n\t\t\t\t7\n\t\t\t<\/td><td>\n\t\t\t\tT : E .\n\t\t\t\t31\n\t\t\t<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h3 class=\"wp-block-heading\"> <strong>Addressing<\/strong> for SLC-500 Remote I\/O (1747-SN)<\/h3>\n\n\n\n<p> Use the chart for addressing.  What address would the following light show up on in the data table if it is wired to terminal 7?<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"659\" height=\"208\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-11.png\" alt=\"\" class=\"wp-image-1980 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-11.png 659w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-11-300x95.png 300w\" data-sizes=\"(max-width: 659px) 100vw, 659px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 659px; --smush-placeholder-aspect-ratio: 659\/208;\" \/><\/figure>\n\n\n\n<p>\nYou should have figured out the address is  <strong>O : 1 . 26 \/ 7<\/strong><\/p>\n\n\n\n<p> Let&#8217;s see this bit in the Data Table:<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" width=\"564\" height=\"185\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-12.png\" alt=\"\" class=\"wp-image-1981 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-12.png 564w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-12-300x98.png 300w\" data-sizes=\"(max-width: 564px) 100vw, 564px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 564px; --smush-placeholder-aspect-ratio: 564\/185;\" \/><\/figure>\n\n\n\n<p>For more information on your particular scanner or adapter, visit <a href=\"http:\/\/ab.com\">AB&#8217;s Web Page.<\/a><\/p>\n\n\n\n<p>If you are interested in more SLC-500 documents, visit the <a href=\"https:\/\/bryceautomation.com\/index.php\/category\/slc500\/\">Category Page!<\/a><\/p>\n\n\n\n<p>&#8212; Ricky Bryce<\/p>\n<div id=\"bryce-1591986451\" class=\"bryce-after-content bryce-entity-placement\"><script async src=\"\/\/pagead2.googlesyndication.com\/pagead\/js\/adsbygoogle.js?client=ca-pub-8316758073402323\" crossorigin=\"anonymous\"><\/script><ins class=\"adsbygoogle\" style=\"display:block;\" data-ad-client=\"ca-pub-8316758073402323\" \ndata-ad-slot=\"4667596182\" \ndata-ad-format=\"auto\"><\/ins>\n<script> \n(adsbygoogle = window.adsbygoogle || []).push({}); \n<\/script>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>Introduction to SLC-500 Remote I\/O (1747-SN) There are many reasons to use SLC-500 Remote I\/O (1747-SN). Imagine a conveyor system. Ten thousand feet from the local processor chassis, you have 256 points of I\/O. With Remote I\/O, you could mount a chassis up to 10,000 feet from the local processor with a Remote I\/O adapter, <a class=\"moretag btn btn-primary\" href=\"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/\">Read More \u00bb<\/a><\/p>\n","protected":false},"author":1,"featured_media":1978,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[130],"tags":[161,160,162,163],"class_list":{"0":"post-1967","1":"post","2":"type-post","3":"status-publish","4":"format-standard","5":"has-post-thumbnail","7":"category-slc500","8":"tag-1747-asb","9":"tag-1747-sn","10":"tag-1771-asb","11":"tag-slc-500-remote-i-o","12":"czr-hentry"},"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.3 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>SLC-500 Remote I\/O (1747-SN) -- 1747-ASB, and 1771-ASB<\/title>\n<meta name=\"description\" content=\"Configuring SLC-500 Remote I\/O (1747-SN). This document covers how to connect and configure the SLC adapter and the PLC-5 adapters.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"SLC-500 Remote I\/O (1747-SN) -- 1747-ASB, and 1771-ASB\" \/>\n<meta property=\"og:description\" content=\"Configuring SLC-500 Remote I\/O (1747-SN). This document covers how to connect and configure the SLC adapter and the PLC-5 adapters.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/\" \/>\n<meta property=\"og:site_name\" content=\"Bryce Automation\" \/>\n<meta property=\"article:author\" content=\"https:\/\/www.facebook.com\/ricky.bryce.7\" \/>\n<meta property=\"article:published_time\" content=\"2019-10-14T23:00:25+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2020-11-30T20:11:30+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9.png\" \/>\n\t<meta property=\"og:image:width\" content=\"450\" \/>\n\t<meta property=\"og:image:height\" content=\"418\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\n<meta name=\"author\" content=\"Ricky\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/\"},\"author\":{\"name\":\"Ricky\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#\\\/schema\\\/person\\\/5d5b0f6f6ad768f1ee52968338e63af7\"},\"headline\":\"SLC-500 Remote I\\\/O (1747-SN)\",\"datePublished\":\"2019-10-14T23:00:25+00:00\",\"dateModified\":\"2020-11-30T20:11:30+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/\"},\"wordCount\":2238,\"commentCount\":2,\"image\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/uploads\\\/2019\\\/10\\\/image-9.png\",\"keywords\":[\"1747-asb\",\"1747-SN\",\"1771-asb\",\"SLC-500 Remote I\\\/O\"],\"articleSection\":[\"SLC500\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/\",\"url\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/\",\"name\":\"SLC-500 Remote I\\\/O (1747-SN) -- 1747-ASB, and 1771-ASB\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/uploads\\\/2019\\\/10\\\/image-9.png\",\"datePublished\":\"2019-10-14T23:00:25+00:00\",\"dateModified\":\"2020-11-30T20:11:30+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#\\\/schema\\\/person\\\/5d5b0f6f6ad768f1ee52968338e63af7\"},\"description\":\"Configuring SLC-500 Remote I\\\/O (1747-SN). This document covers how to connect and configure the SLC adapter and the PLC-5 adapters.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/#primaryimage\",\"url\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/uploads\\\/2019\\\/10\\\/image-9.png\",\"contentUrl\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/uploads\\\/2019\\\/10\\\/image-9.png\",\"width\":450,\"height\":418,\"caption\":\"G-File\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2019\\\/10\\\/14\\\/slc-500-remote-i-o\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/bryceautomation.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"SLC-500 Remote I\\\/O (1747-SN)\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#website\",\"url\":\"https:\\\/\\\/bryceautomation.com\\\/\",\"name\":\"Bryce Automation\",\"description\":\"Automating Home and Industry...\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/bryceautomation.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#\\\/schema\\\/person\\\/5d5b0f6f6ad768f1ee52968338e63af7\",\"name\":\"Ricky\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/wphb-cache\\\/gravatar\\\/a8f\\\/a8fe6bf79d292b388ffee281ccb12488x96.jpg\",\"url\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/wphb-cache\\\/gravatar\\\/a8f\\\/a8fe6bf79d292b388ffee281ccb12488x96.jpg\",\"contentUrl\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/wphb-cache\\\/gravatar\\\/a8f\\\/a8fe6bf79d292b388ffee281ccb12488x96.jpg\",\"caption\":\"Ricky\"},\"sameAs\":[\"http:\\\/\\\/bryceautomation.com\",\"https:\\\/\\\/www.facebook.com\\\/ricky.bryce.7\",\"https:\\\/\\\/www.linkedin.com\\\/in\\\/ricky-bryce-4367a416\\\/\"],\"url\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/author\\\/ricky\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"SLC-500 Remote I\/O (1747-SN) -- 1747-ASB, and 1771-ASB","description":"Configuring SLC-500 Remote I\/O (1747-SN). This document covers how to connect and configure the SLC adapter and the PLC-5 adapters.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/","og_locale":"en_US","og_type":"article","og_title":"SLC-500 Remote I\/O (1747-SN) -- 1747-ASB, and 1771-ASB","og_description":"Configuring SLC-500 Remote I\/O (1747-SN). This document covers how to connect and configure the SLC adapter and the PLC-5 adapters.","og_url":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/","og_site_name":"Bryce Automation","article_author":"https:\/\/www.facebook.com\/ricky.bryce.7","article_published_time":"2019-10-14T23:00:25+00:00","article_modified_time":"2020-11-30T20:11:30+00:00","og_image":[{"width":450,"height":418,"url":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9.png","type":"image\/png"}],"author":"Ricky","twitter_card":"summary_large_image","schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/#article","isPartOf":{"@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/"},"author":{"name":"Ricky","@id":"https:\/\/bryceautomation.com\/#\/schema\/person\/5d5b0f6f6ad768f1ee52968338e63af7"},"headline":"SLC-500 Remote I\/O (1747-SN)","datePublished":"2019-10-14T23:00:25+00:00","dateModified":"2020-11-30T20:11:30+00:00","mainEntityOfPage":{"@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/"},"wordCount":2238,"commentCount":2,"image":{"@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/#primaryimage"},"thumbnailUrl":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9.png","keywords":["1747-asb","1747-SN","1771-asb","SLC-500 Remote I\/O"],"articleSection":["SLC500"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/","url":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/","name":"SLC-500 Remote I\/O (1747-SN) -- 1747-ASB, and 1771-ASB","isPartOf":{"@id":"https:\/\/bryceautomation.com\/#website"},"primaryImageOfPage":{"@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/#primaryimage"},"image":{"@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/#primaryimage"},"thumbnailUrl":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9.png","datePublished":"2019-10-14T23:00:25+00:00","dateModified":"2020-11-30T20:11:30+00:00","author":{"@id":"https:\/\/bryceautomation.com\/#\/schema\/person\/5d5b0f6f6ad768f1ee52968338e63af7"},"description":"Configuring SLC-500 Remote I\/O (1747-SN). This document covers how to connect and configure the SLC adapter and the PLC-5 adapters.","breadcrumb":{"@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/#primaryimage","url":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9.png","contentUrl":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2019\/10\/image-9.png","width":450,"height":418,"caption":"G-File"},{"@type":"BreadcrumbList","@id":"https:\/\/bryceautomation.com\/index.php\/2019\/10\/14\/slc-500-remote-i-o\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/bryceautomation.com\/"},{"@type":"ListItem","position":2,"name":"SLC-500 Remote I\/O (1747-SN)"}]},{"@type":"WebSite","@id":"https:\/\/bryceautomation.com\/#website","url":"https:\/\/bryceautomation.com\/","name":"Bryce Automation","description":"Automating Home and Industry...","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/bryceautomation.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Person","@id":"https:\/\/bryceautomation.com\/#\/schema\/person\/5d5b0f6f6ad768f1ee52968338e63af7","name":"Ricky","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/bryceautomation.com\/wp-content\/wphb-cache\/gravatar\/a8f\/a8fe6bf79d292b388ffee281ccb12488x96.jpg","url":"https:\/\/bryceautomation.com\/wp-content\/wphb-cache\/gravatar\/a8f\/a8fe6bf79d292b388ffee281ccb12488x96.jpg","contentUrl":"https:\/\/bryceautomation.com\/wp-content\/wphb-cache\/gravatar\/a8f\/a8fe6bf79d292b388ffee281ccb12488x96.jpg","caption":"Ricky"},"sameAs":["http:\/\/bryceautomation.com","https:\/\/www.facebook.com\/ricky.bryce.7","https:\/\/www.linkedin.com\/in\/ricky-bryce-4367a416\/"],"url":"https:\/\/bryceautomation.com\/index.php\/author\/ricky\/"}]}},"_links":{"self":[{"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/posts\/1967","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/comments?post=1967"}],"version-history":[{"count":0,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/posts\/1967\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/media\/1978"}],"wp:attachment":[{"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/media?parent=1967"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/categories?post=1967"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/tags?post=1967"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}