{"id":3311,"date":"2020-11-23T20:24:54","date_gmt":"2020-11-23T20:24:54","guid":{"rendered":"http:\/\/bryceautomation.com\/?p=3311"},"modified":"2020-11-24T01:02:25","modified_gmt":"2020-11-24T01:02:25","slug":"controllogix-message-to-plc-2","status":"publish","type":"post","link":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/","title":{"rendered":"ControlLogix Message to PLC-2"},"content":{"rendered":"\n<h4 class=\"wp-block-heading\">Introduction &#8212; ControlLogix Message to PLC-2 Processor<\/h4>\n\n\n\n<p>In this section, we&#8217;ll cover how to send a ControlLogix Message to the PLC-2.   The PLC-2 is now old, and obsolete.   However, there are still quite a few systems that exist, and we need to get data from them.   In this case, we&#8217;ll send 3 words to a PLC-2.  The PLC-2 is connected to the Data Highway Plus network through a 1785-KA3 module.  The KA3 Module is set for Node 5. Likewise, the 1756-DHRIO module (Channel A) is at Node 26 on the DH+ Network.<\/p><div id=\"bryce-490321\" class=\"bryce-afterfirst bryce-entity-placement\"><script async src=\"\/\/pagead2.googlesyndication.com\/pagead\/js\/adsbygoogle.js?client=ca-pub-8316758073402323\" crossorigin=\"anonymous\"><\/script><ins class=\"adsbygoogle\" style=\"display:block;\" data-ad-client=\"ca-pub-8316758073402323\" \ndata-ad-slot=\"7728240895\" \ndata-ad-format=\"auto\"><\/ins>\n<script> \n(adsbygoogle = window.adsbygoogle || []).push({}); \n<\/script>\n<\/div>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"522\" height=\"468\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-14.png\" alt=\"\" class=\"wp-image-3312 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-14.png 522w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-14-300x269.png 300w\" data-sizes=\"(max-width: 522px) 100vw, 522px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 522px; --smush-placeholder-aspect-ratio: 522\/468;\" \/><\/figure>\n\n\n\n<h4 class=\"wp-block-heading\">Create the Tags<\/h4>\n\n\n\n<p>First, in the ControlLogix processor, we&#8217;ll create some tags that will allow our message instruction to operate.   Under &#8220;Edit Tags&#8221;, create the following tags in the controller tag database:<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"431\" height=\"161\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-20.png\" alt=\"\" class=\"wp-image-3320 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-20.png 431w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-20-300x112.png 300w\" data-sizes=\"(max-width: 431px) 100vw, 431px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 431px; --smush-placeholder-aspect-ratio: 431\/161;\" \/><\/figure>\n\n\n\n<p>We&#8217;ll use the tag &#8220;msgTimer&#8221; to trigger the message instruction in logic.  In contrast, we&#8217;ll use &#8220;msgControl&#8221; as the workspace of our message instruction.  Lastly, the tag &#8220;DataToPLC2&#8221; will contain the data we wish to send to the PLC-2\/17 processor at Node 5.  Meanwhile, let&#8217;s go to &#8220;Monitor Tags&#8221;, and populate the tag with random values to see if they later arrive at the target processor.  Just remember this is a PLC-2, so I&#8217;m not going to send over 3 words, and the values will not exceed 8 bits (255 decimal).<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"386\" height=\"196\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-21.png\" alt=\"\" class=\"wp-image-3321 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-21.png 386w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-21-300x152.png 300w\" data-sizes=\"(max-width: 386px) 100vw, 386px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 386px; --smush-placeholder-aspect-ratio: 386\/196;\" \/><\/figure>\n\n\n\n<h4 class=\"wp-block-heading\">Add the logic for messaging your PLC-2<\/h4>\n\n\n\n<p>In Short, we&#8217;ll add the following logic to the MainRoutine.   The timer will reset itself every 100ms, and trigger our message instruction.<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"504\" height=\"216\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-17.png\" alt=\"\" class=\"wp-image-3316 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-17.png 504w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-17-300x129.png 300w\" data-sizes=\"(max-width: 504px) 100vw, 504px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 504px; --smush-placeholder-aspect-ratio: 504\/216;\" \/><\/figure>\n\n\n\n<p>At last, we&#8217;ll configure the message instruction.  Within the message block, click the &#8220;&#8230;&#8221; (grey button) to access the configuration screen.  Notice our type is &#8220;PLC2 Unprotected Write&#8221;.  The Source is &#8220;DataToPLC2[0]&#8221;, which is the first element we are getting data from.  In the PLC2 processor, we&#8217;ll write to memory location &#8220;120&#8221;.<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"526\" height=\"374\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-22.png\" alt=\"\" class=\"wp-image-3322 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-22.png 526w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-22-300x213.png 300w\" data-sizes=\"(max-width: 526px) 100vw, 526px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 526px; --smush-placeholder-aspect-ratio: 526\/374;\" \/><\/figure>\n\n\n\n<p>Next, we have to set the path, so go to the &#8220;Communication&#8221; Tab.  In this case, the path is 1,2.  The 1 gets us to the backplane from the processor.  The next part of our path is &#8220;2&#8221;, for Slot 2.  Once we are on the DHRIO module, we&#8217;ll pick up the communication method of DH+.  Be sure to select the DH+ Radio button.   Generally, we set Channel A to DH+.  In brief, the mode of a channel and it&#8217;s node number are a hardware setting on the DHRIO module itself.  The destination node is &#8220;5&#8221;.  We set this by DIP switches on the KA3 module in the PLC-2 chassis.  A 1771-CO cable connects the KA3 module to the programming port of the PLC2 processor.<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"520\" height=\"374\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-19.png\" alt=\"\" class=\"wp-image-3319 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-19.png 520w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-19-300x216.png 300w\" data-sizes=\"(max-width: 520px) 100vw, 520px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 520px; --smush-placeholder-aspect-ratio: 520\/374;\" \/><\/figure>\n\n\n\n<h4 class=\"wp-block-heading\">Download and test your work<\/h4>\n\n\n\n<p>Finally we are ready for the real test.   We&#8217;ll download to the ControlLogix processor.  At last, we&#8217;ll check the Data Table in the PLC2 to verify it received the proper data from the ControlLogix processor.<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"646\" height=\"328\" data-src=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-23.png\" alt=\"\" class=\"wp-image-3323 lazyload\" data-srcset=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-23.png 646w, https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-23-300x152.png 300w\" data-sizes=\"(max-width: 646px) 100vw, 646px\" src=\"data:image\/svg+xml;base64,PHN2ZyB3aWR0aD0iMSIgaGVpZ2h0PSIxIiB4bWxucz0iaHR0cDovL3d3dy53My5vcmcvMjAwMC9zdmciPjwvc3ZnPg==\" style=\"--smush-placeholder-width: 646px; --smush-placeholder-aspect-ratio: 646\/328;\" \/><\/figure>\n\n\n\n<p>For more information, visit the <a href=\"https:\/\/bryceautomation.com\/index.php\/category\/controllogix\/\">ControlLogix Category Page!<\/a><\/p>\n\n\n\n<p>&#8212; Ricky Bryce<\/p>\n<div id=\"bryce-3906611792\" class=\"bryce-after-content bryce-entity-placement\"><script async src=\"\/\/pagead2.googlesyndication.com\/pagead\/js\/adsbygoogle.js?client=ca-pub-8316758073402323\" crossorigin=\"anonymous\"><\/script><ins class=\"adsbygoogle\" style=\"display:block;\" data-ad-client=\"ca-pub-8316758073402323\" \ndata-ad-slot=\"4667596182\" \ndata-ad-format=\"auto\"><\/ins>\n<script> \n(adsbygoogle = window.adsbygoogle || []).push({}); \n<\/script>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>Introduction &#8212; ControlLogix Message to PLC-2 Processor In this section, we&#8217;ll cover how to send a ControlLogix Message to the PLC-2. The PLC-2 is now old, and obsolete. However, there are still quite a few systems that exist, and we need to get data from them. In this case, we&#8217;ll send 3 words to a <a class=\"moretag btn btn-primary\" href=\"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/\">Read More \u00bb<\/a><\/p>\n","protected":false},"author":1,"featured_media":3323,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[4],"tags":[140,215,259],"class_list":{"0":"post-3311","1":"post","2":"type-post","3":"status-publish","4":"format-standard","5":"has-post-thumbnail","7":"category-controllogix","8":"tag-messaging","9":"tag-msg","10":"tag-plc-2","11":"czr-hentry"},"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.4 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>ControlLogix Message to PLC-2 - Bryce Automation<\/title>\n<meta name=\"description\" content=\"How to set up a ControlLogix Message to PLC-2. We&#039;ll send 3 words from the ControlLogix to a PLC 2\/17 processor over a DH+ Network.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"ControlLogix Message to PLC-2 - Bryce Automation\" \/>\n<meta property=\"og:description\" content=\"How to set up a ControlLogix Message to PLC-2. We&#039;ll send 3 words from the ControlLogix to a PLC 2\/17 processor over a DH+ Network.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/\" \/>\n<meta property=\"og:site_name\" content=\"Bryce Automation\" \/>\n<meta property=\"article:author\" content=\"https:\/\/www.facebook.com\/ricky.bryce.7\" \/>\n<meta property=\"article:published_time\" content=\"2020-11-23T20:24:54+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2020-11-24T01:02:25+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-23.png\" \/>\n\t<meta property=\"og:image:width\" content=\"646\" \/>\n\t<meta property=\"og:image:height\" content=\"328\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\n<meta name=\"author\" content=\"Ricky\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/\"},\"author\":{\"name\":\"Ricky\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#\\\/schema\\\/person\\\/5d5b0f6f6ad768f1ee52968338e63af7\"},\"headline\":\"ControlLogix Message to PLC-2\",\"datePublished\":\"2020-11-23T20:24:54+00:00\",\"dateModified\":\"2020-11-24T01:02:25+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/\"},\"wordCount\":476,\"commentCount\":0,\"image\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/uploads\\\/2020\\\/11\\\/image-23.png\",\"keywords\":[\"Messaging\",\"msg\",\"plc-2\"],\"articleSection\":[\"ControlLogix\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/\",\"url\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/\",\"name\":\"ControlLogix Message to PLC-2 - Bryce Automation\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/uploads\\\/2020\\\/11\\\/image-23.png\",\"datePublished\":\"2020-11-23T20:24:54+00:00\",\"dateModified\":\"2020-11-24T01:02:25+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#\\\/schema\\\/person\\\/5d5b0f6f6ad768f1ee52968338e63af7\"},\"description\":\"How to set up a ControlLogix Message to PLC-2. We'll send 3 words from the ControlLogix to a PLC 2\\\/17 processor over a DH+ Network.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/#primaryimage\",\"url\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/uploads\\\/2020\\\/11\\\/image-23.png\",\"contentUrl\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/uploads\\\/2020\\\/11\\\/image-23.png\",\"width\":646,\"height\":328,\"caption\":\"PLC2 Message\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/2020\\\/11\\\/23\\\/controllogix-message-to-plc-2\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/bryceautomation.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"ControlLogix Message to PLC-2\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#website\",\"url\":\"https:\\\/\\\/bryceautomation.com\\\/\",\"name\":\"Bryce Automation\",\"description\":\"Automating Home and Industry...\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/bryceautomation.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/#\\\/schema\\\/person\\\/5d5b0f6f6ad768f1ee52968338e63af7\",\"name\":\"Ricky\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/wphb-cache\\\/gravatar\\\/a8f\\\/a8fe6bf79d292b388ffee281ccb12488x96.jpg\",\"url\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/wphb-cache\\\/gravatar\\\/a8f\\\/a8fe6bf79d292b388ffee281ccb12488x96.jpg\",\"contentUrl\":\"https:\\\/\\\/bryceautomation.com\\\/wp-content\\\/wphb-cache\\\/gravatar\\\/a8f\\\/a8fe6bf79d292b388ffee281ccb12488x96.jpg\",\"caption\":\"Ricky\"},\"sameAs\":[\"http:\\\/\\\/bryceautomation.com\",\"https:\\\/\\\/www.facebook.com\\\/ricky.bryce.7\",\"https:\\\/\\\/www.linkedin.com\\\/in\\\/ricky-bryce-4367a416\\\/\"],\"url\":\"https:\\\/\\\/bryceautomation.com\\\/index.php\\\/author\\\/ricky\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"ControlLogix Message to PLC-2 - Bryce Automation","description":"How to set up a ControlLogix Message to PLC-2. We'll send 3 words from the ControlLogix to a PLC 2\/17 processor over a DH+ Network.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/","og_locale":"en_US","og_type":"article","og_title":"ControlLogix Message to PLC-2 - Bryce Automation","og_description":"How to set up a ControlLogix Message to PLC-2. We'll send 3 words from the ControlLogix to a PLC 2\/17 processor over a DH+ Network.","og_url":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/","og_site_name":"Bryce Automation","article_author":"https:\/\/www.facebook.com\/ricky.bryce.7","article_published_time":"2020-11-23T20:24:54+00:00","article_modified_time":"2020-11-24T01:02:25+00:00","og_image":[{"width":646,"height":328,"url":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-23.png","type":"image\/png"}],"author":"Ricky","twitter_card":"summary_large_image","schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/#article","isPartOf":{"@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/"},"author":{"name":"Ricky","@id":"https:\/\/bryceautomation.com\/#\/schema\/person\/5d5b0f6f6ad768f1ee52968338e63af7"},"headline":"ControlLogix Message to PLC-2","datePublished":"2020-11-23T20:24:54+00:00","dateModified":"2020-11-24T01:02:25+00:00","mainEntityOfPage":{"@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/"},"wordCount":476,"commentCount":0,"image":{"@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/#primaryimage"},"thumbnailUrl":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-23.png","keywords":["Messaging","msg","plc-2"],"articleSection":["ControlLogix"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/","url":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/","name":"ControlLogix Message to PLC-2 - Bryce Automation","isPartOf":{"@id":"https:\/\/bryceautomation.com\/#website"},"primaryImageOfPage":{"@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/#primaryimage"},"image":{"@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/#primaryimage"},"thumbnailUrl":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-23.png","datePublished":"2020-11-23T20:24:54+00:00","dateModified":"2020-11-24T01:02:25+00:00","author":{"@id":"https:\/\/bryceautomation.com\/#\/schema\/person\/5d5b0f6f6ad768f1ee52968338e63af7"},"description":"How to set up a ControlLogix Message to PLC-2. We'll send 3 words from the ControlLogix to a PLC 2\/17 processor over a DH+ Network.","breadcrumb":{"@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/#primaryimage","url":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-23.png","contentUrl":"https:\/\/bryceautomation.com\/wp-content\/uploads\/2020\/11\/image-23.png","width":646,"height":328,"caption":"PLC2 Message"},{"@type":"BreadcrumbList","@id":"https:\/\/bryceautomation.com\/index.php\/2020\/11\/23\/controllogix-message-to-plc-2\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/bryceautomation.com\/"},{"@type":"ListItem","position":2,"name":"ControlLogix Message to PLC-2"}]},{"@type":"WebSite","@id":"https:\/\/bryceautomation.com\/#website","url":"https:\/\/bryceautomation.com\/","name":"Bryce Automation","description":"Automating Home and Industry...","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/bryceautomation.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Person","@id":"https:\/\/bryceautomation.com\/#\/schema\/person\/5d5b0f6f6ad768f1ee52968338e63af7","name":"Ricky","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/bryceautomation.com\/wp-content\/wphb-cache\/gravatar\/a8f\/a8fe6bf79d292b388ffee281ccb12488x96.jpg","url":"https:\/\/bryceautomation.com\/wp-content\/wphb-cache\/gravatar\/a8f\/a8fe6bf79d292b388ffee281ccb12488x96.jpg","contentUrl":"https:\/\/bryceautomation.com\/wp-content\/wphb-cache\/gravatar\/a8f\/a8fe6bf79d292b388ffee281ccb12488x96.jpg","caption":"Ricky"},"sameAs":["http:\/\/bryceautomation.com","https:\/\/www.facebook.com\/ricky.bryce.7","https:\/\/www.linkedin.com\/in\/ricky-bryce-4367a416\/"],"url":"https:\/\/bryceautomation.com\/index.php\/author\/ricky\/"}]}},"_links":{"self":[{"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/posts\/3311","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/comments?post=3311"}],"version-history":[{"count":0,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/posts\/3311\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/media\/3323"}],"wp:attachment":[{"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/media?parent=3311"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/categories?post=3311"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/bryceautomation.com\/index.php\/wp-json\/wp\/v2\/tags?post=3311"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}